MINOS SLxD | |
---|---|
Safety function | Safety emergency stop, safety doors, light curtains, contact reinforcement, OSSD, continous operation of furnaces , stopp category 0 |
Certified according to | EN ISO 13849-1; IEC 62061; IEC 61508; EN 50156-1; EN 746-2IEC 61511-1; EN 60204-1 |
Approvals | CE, TUV |
Supply Voltage | UB: DC 24 V (+/- 10 %) |
Power consumption at UB = 24V | 2.4 W (module enabled via S11. No load) |
Number dual-channel inputs | 1 |
Number start input | 1 (auto-start or manual start each variant) |
Max. switching capacity O1 ut UB. | max. 2.5 A (see derating in the operating instructions) |
Maximum switching capacity auxiliary output C1 | max. 100 mA |
Max. switch-on delay | 10 ms |
Off-delay (if requested via the safety circuit) | < 13 ms |
Ambient temperatur | -15 °C to 55 °C (see derating in the operating instructions) |
Protection | IP20 |
Mounting | 35 mm DIN-rail |
PL; Kat.; SILCL (EN ISO 13849-1; EN 62061) | PL d; SILCL 2 |
Dimension | 6.2 x 93.1 x 102.5 mm |
Manual Start: | 50 g |
Manueller Start: | |
MINOS SL1D, tensil spring terminal, manual start | 472800 |
MINOS SL1D, screw terminal,manual start | 472801 |
MINOS SL2D, tensil spring terminal, manual start | 472804 |
MINOS SL2D, screw terminal, manual start | 472805 |
Auto-Start: | |
MINOS SL1D, tensil spring terminal, auto-start | 472802 |
MINOS SL1D, screw terminal, auto-start | 472803 |
MINOS SL2D, tensil spring terminal, auto-start | 472806 |
MINOS SL2D, screw terminal, auto-start | 472807 |
Zander Aachen MINOS SLxD - EN 50156-1 Safe Firing
Zander Aachen MINOS SLxD - EN 50156-1 Safe Firing
Code: MINOS SLxD - EN 50156-1
Brand: Zander Aachen
MINOS SLxD are safety emergency stop modules for monitoring emergency stop buttons, safety doors and light curtains, as well as contact reinforcement of safe outputs (e.g. safe PLC outputs) to machines and plants.
The modules are also certified for continuous operation in furnaces according to EN 50156-1 as well as EN 746-2. For use in the process industry these modules are certified according to IEC 61511-1.
SLxD:
Variant for max. requirements up to PL d / SILCL 2 (according to EN ISO 13849-1 bzw. IEC 62061). Test pulses at the safe output enable error detection during operation.
SL1D for dual-channel emergency stop circuit, safety door monitoring with short circuit monitoring
SL2D for light curtains, OSSD output or single-channel emergency stop
There are variants with manual start or auto-start.
These Module are available with screw terminals or tensile spring terminals.
Zander Aachen Datasheets
Country & Language | File Name | Download Link |
United States (English) | Zander-Aachen-EN_42085.pdf | Download |
Contact Sales
Drop us a call on our Phone or by E-Mail with 24/7 basis. We will get back to you shortly in business days.
Contact & Support
Request a Quote