General information
Order number600-222-0AD21
Article nameDO 4x relays, 5 A, AC 230 V, changeover
Scope of deliveryDO 4x relays, 5 A, AC 230 V, changeover
Dimensions (DxWxH)110 x 25 x 73 mm
WeightApprox. 120 g
Number of outputs8 (four changeover relays)
Electrical isolation
from the backplane busYes
Between the channelsYes
Supply voltage UP, US
Rated value24 V DC
Ripple USSmax. 3.6 V
Permissible range (with ripple)20 … 30 V
Voltage for t < 10 ms50 V
Current draw
ExternalMax. 60 mA
InternalMax. 60 mA
Relays
Number4
Max. continuous current / max. inrush current5 A/10 A
Rated voltage / max. switching voltage250 V AC/400 V AC
Max. switching power for utilization category AC-11500 VA
Max. switching power AC15 (230 V AC)300 VA
Single-phase motor load, AC3 – running (230 V AC)0.185 kW
Max. switching current for utilization category DC-1: 30/110/220 V6/0.2/0.12 A
Min. switching capacity500 mW (12 V/10 mA)
Mechanical life10 * 106 switching operations
Electrical life for utilization category AC-160000 switching operations
Dielectric strength, coil to contact6 kV (8 mm)
Dielectric strength across open contacts1000 V AC
Max. switching frequency (internal protection)10 Hz
Hot-swap capableYes
Ambient conditions
Ambient temperature0 °C … +60 °C
Transport and storage temperature-20 °C … +80 °C
Relative air humidity95 % r H without condensation
Protection ratingIP 20
CertificationsCE, UL
UL
Surrounding Air Temperature0 °C … +60°C
Pollution degree2
CE
Noise immunityDIN EN 61000-6-2 “EMC Immunity”
Interference emissionDIN EN 61000-6-4 “EMC Emission”
Vibration and shock resistanceDIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock"
RoHSYes
REACHYes