Helmholz 600-222-0AD21 DO 4x relays, 5 A, AC 230 V, changeover Module
Helmholz 600-222-0AD21 DO 4x relays, 5 A, AC 230 V, changeover Module
Código: 600-222-0AD21
Marca: Helmholz
General information | ||
---|---|---|
Order number | 600-222-0AD21 | |
Article name | DO 4x relays, 5 A, AC 230 V, changeover | |
Scope of delivery | DO 4x relays, 5 A, AC 230 V, changeover | |
Dimensions (DxWxH) | 110 x 25 x 73 mm | |
Weight | Approx. 120 g | |
Number of outputs | 8 (four changeover relays) | |
Electrical isolation | ||
from the backplane bus | Yes | |
Between the channels | Yes | |
Supply voltage UP, US | ||
Rated value | 24 V DC | |
Ripple USS | max. 3.6 V | |
Permissible range (with ripple) | 20 … 30 V | |
Voltage for t < 10 ms | 50 V | |
Current draw | ||
External | Max. 60 mA | |
Internal | Max. 60 mA | |
Relays | ||
Number | 4 | |
Max. continuous current / max. inrush current | 5 A/10 A | |
Rated voltage / max. switching voltage | 250 V AC/400 V AC | |
Max. switching power for utilization category AC-1 | 1500 VA | |
Max. switching power AC15 (230 V AC) | 300 VA | |
Single-phase motor load, AC3 – running (230 V AC) | 0.185 kW | |
Max. switching current for utilization category DC-1: 30/110/220 V | 6/0.2/0.12 A | |
Min. switching capacity | 500 mW (12 V/10 mA) | |
Mechanical life | 10 * 106 switching operations | |
Electrical life for utilization category AC-1 | 60000 switching operations | |
Dielectric strength, coil to contact | 6 kV (8 mm) | |
Dielectric strength across open contacts | 1000 V AC | |
Max. switching frequency (internal protection) | 10 Hz | |
Hot-swap capable | Yes | |
Ambient conditions | ||
Ambient temperature | 0 °C … +60 °C | |
Transport and storage temperature | -20 °C … +80 °C | |
Relative air humidity | 95 % r H without condensation | |
Protection rating | IP 20 | |
Certifications | CE, UL | |
UL | ||
Surrounding Air Temperature | 0 °C … +60°C | |
Pollution degree | 2 | |
CE | ||
Noise immunity | DIN EN 61000-6-2 “EMC Immunity” | |
Interference emission | DIN EN 61000-6-4 “EMC Emission” | |
Vibration and shock resistance | DIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock" | |
RoHS | Yes | |
REACH | Yes |