MINOS SLxD | |
---|---|
Safety function | Safety emergency stop, safety doors, light curtains, contact reinforcement, OSSD, for furnaces in continuous operation, stopp category 0 |
Certified according to | EN ISO 13849-1; IEC 62061; IEC 61508; EN 50156-1; EN 746-2IEC 61511-1; EN 60204-1 |
PL; Cat.; SILCL (EN ISO 13849-1; EN 62061) | PL d; Cat. 3; SILCL 2 |
Approvals | CE, TUV, UL |
Supply Voltage | UB: DC 24 V (+/- 10 %) |
Power consumption at UB = 24V | 1.8 W (module enabled via S11. No load) |
Number dual-channel inputs | 1 |
Number start input | 1 (auto-start or manual start each variant) |
Max. switching capacity O1 ut UB. | max. 2.5 A (see derating in the operating instructions) |
Maximum switching capacity auxiliary output C1 | max. 100 mA |
Max. switch-on delay | 10 ms |
Off-delay (if requested via the safety circuit) | < 13 ms |
Ambient temperatur | -15 °C to 55 °C (see derating in the operating instructions) |
Protection | IP20 |
Mounting | 35 mm DIN-rail |
Dimensions | 6.2 x 93.1 x 102.5 mm |
Manual Start: | 50 g |
Manual Start: | |
MINOS SL1D, tensil spring terminal, manual start | 472800 |
MINOS SL1D, screw terminal,manual start | 472801 |
MINOS SL2D, tensil spring terminal, manual start | 472804 |
MINOS SL2D, screw terminal, manual start | 472805 |
Automatic Start: | |
MINOS SL1D, tensil spring terminal, auto-start | 472802 |
MINOS SL1D, screw terminal, auto-start | 472803 |
MINOS SL2D, tensil spring terminal, auto-start | 472806 |
MINOS SL2D, screw terminal, auto-start | 472807 |
Zander Aachen MINOS SLxD Ultra Slim Safety Relay
Zander Aachen MINOS SLxD Ultra Slim Safety Relay
Codice: MINOS SLxD
Marchio: Zander Aachen
MINOS SLxD are safety emergency stop relays for monitoring emergency stop buttons, safety doors and light curtains, as well as contact reinforcement of safe outputs (e.g. safe PLC outputs) to machines and plants.
The modules are also certified for furnaces in continuous operation according to EN 50156-1 as well as EN 746-2. For use in the process industry these modules are certified according to IEC 61511-1.
SLxD:
Variant for max. requirements up to PL d / Cat.3 / SILCL 2 (according to EN ISO 13849-1; IEC 62061).
SL1D for dual-channel emergency stop circuit, safety door monitoring with short circuit monitoring
SL2D for light curtains, contact reinforcement, OSSD output or single-channel emergency stop
There are variants with manual start or auto-start.
These Module are available with screw terminals or tensile spring terminals.
Zander Aachen Datasheet
Paese e lingua | Nome del file | Link di download |
United States (English) | Zander-Aachen-EN_42085.pdf | Download |
Contact Sales
Chiamateci al telefono o per e-mail, 24 ore su 24, 7 giorni su 7. Vi risponderemo in breve tempo. Vi risponderemo entro pochi giorni lavorativi.
Contatti e assistenza
Richiedi un preventivo