Stego FPI/FPO 018 | UP TO 24 M³/H (92 X 92 MM) Filter Fan Plus

  • Stego FPI/FPO 018 | UP TO 24 M³/H (92 X 92 MM) Filter Fan Plus

Stego FPI/FPO 018 | UP TO 24 M³/H (92 X 92 MM) Filter Fan Plus

Code: FPI/FPO 018 | UP TO 24 M³/H (92 X 92 MM)
Marque: Stego

Axial fan, ball bearing service life L10 at +40 °C (+104 °F): min. 50,000 h
fan body aluminium, rotor metal
Connection 2 stranded wires, 300 mm
Casing, hood, flaps plastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out 92 x 92+1 mm
Mounting frame 4 built-in ratchet braces for mounting
(6 notches for wall thickness 1-4 mm).
Additional use of screws possible if needed1.
Filter mat ISO coarse 55 % acc. to ISO 16890 (G3),
initial gravimetric arrestance 57 %
Filter material synthetic fibre with progressive construction, temperature
resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH, reusable
Operating/Storage temperature -40 to +70 °C (-40 to +158 °F)
Operating/Storage humidity max. 90 % RH (non-condensing)
Protection type/Protection class

IP54 / I (earthed)

Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
Approvals VDE, UL File No. E234324, EAC
Note other voltages on request

1 Drilling marks for screw mounting are indicated on mounting frame.

AIRFLOW DIRECTION "IN": FILTER FAN FPI 018

Art. No. Operating voltage Air volume,
free flow
Air volume
with exit filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01870.0-30 AC 230 V, 50/60 Hz 19 m³/h 13 m³/h 70 mA 12 W 39 dB (A) 66 mm 0.6 kg G3
01870.9-30 AC 115 V, 50/60 Hz 23 m³/h 16 m³/h 115 mA 11 W 43 dB (A) 66 mm 0.6 kg G3

AIRFLOW DIRECTION "IN": EXIT FILTER FPI 118

Art. No. Depth in enclosure Weight (approx.) Air outlet
11870.0-00 29 mm 0.2 kg air-flap outlet technology

AIRFLOW DIRECTION "OUT": FILTER FAN FPO 018

Art. No. Operating
voltage
Air volume,
free flow
Air volume
with intake
filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01880.0-00 AC 230 V, 50/60 Hz 24 m³/h 15 m³/h 70 mA 12 W 38 dB (A) 72 mm 0.6 kg air-flaps
01880.9-00 AC 115 V, 50/60 Hz 32 m³/h 19 m³/h 115 mA 12 W 41 dB (A) 72 mm 0.6 kg air-flaps

AIRFLOW DIRECTION "OUT": INTAKE FILTER FPO 118

Art. No. Depth in enclosure Weight (approx.) Filter mat
11880.0-30 22 mm

0.2 kg

ISO coarse 55 % acc. to ISO 16890 (G3), initial gravimetric arrestance 57 %

FILTER MAT FM 086

Filter class 84 x 84 mm Initial gravimetric arrestance 1 packing unit
ISO coarse 55 % acc. to ISO 16890 (G3) Art. No. 08633.0-00 57 % 5 pieces

TECHNICAL DRAWINGS

FPI 018/FPI 118
FPO 018/FPO 11

Stego Fiches techniques

Pays et langue Nom du fichier Lien de téléchargement
United States (English) stego-EN_54310.pdf Télécharger
Deutschland (Deutsch) stego-DE_71351.pdf Télécharger
Italy (Italiano) stego-IT_60429.pdf Télécharger

Demande de devis

Top