Stego FPI/FPO 018 | UP TO 125 M³/H (124 X 124 MM) Filter Fan Plus - DC Line

  • Stego FPI/FPO 018 | UP TO 125 M³/H (124 X 124 MM) Filter Fan Plus - DC Line

Stego FPI/FPO 018 | UP TO 125 M³/H (124 X 124 MM) Filter Fan Plus - DC Line

Code: FPI/FPO 018 | UP TO 125 M³/H (124 X 124 MM)
Marque: Stego

Axial fan, ball bearing service life L10 at +40 °C (+104 °F): min. 65,000 h
plastic
Connection 2 stranded wires, 300 mm
Casing, hood, flaps plastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out 124 x 124+1 mm
Mounting frame 4 built-in ratchet braces for mounting
(6 notches for wall thickness 1-4 mm).
Additional use of screws possible if needed1.
Filter mat ISO coarse 55 % acc. to ISO 16890 (G3),
initial gravimetric arrestance 57 %
Filter material synthetic fibre with progressive construction, temperature
resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH, reusable
Operating temperature -20 to +70 °C (-4 to +158 °F)
Storage temperature -40 to +70 °C (-40 to +158 °F)
Operating/Storage humidity max. 90 % RH (non-condensing)
Protection type/Protection class IP54 / II (double insulated)
Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
Approvals VDE, UL File No. E234324, EAC
Note other voltages on request

1 Drilling marks for screw mounting are indicated on mounting frame.

AIRFLOW DIRECTION "IN": FILTER FAN FPI 018

Art. No. Operating voltage Air volume,
free flow
Air volume
with exit filter
Current
consumption
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01871.2-30 DC 24 V 66 m³/h 56 m³/h 171 mA 4.1 W 58 dB (A) 66 mm 0.5 kg G3
01871.1-30 DC 48 V 67 m³/h 56 m³/h 88 mA 4.2 W 52 dB (A) 66 mm 0.5 kg G3

AIRFLOW DIRECTION "IN": EXIT FILTER FPI 118

Art. No. Depth in enclosure Weight (approx.) Air outlet
11871.0-00 35 mm 0.3 kg air-flap outlet technology

AIRFLOW DIRECTION "OUT": FILTER FAN FPO 018

Art. No. Operating
voltage
Air volume,
free flow
Air volume
with intake filter
Current
consumption
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01881.2-00 DC 24 V 118 m³/h 63 m³/h 171 mA 4.1 W 56 dB (A) 79 mm 0.5 kg air-flaps
01881.1-00 DC 48 V 125 m³/h 63 m³/h 88 mA 4.2 W 60 dB (A) 79 mm 0.5 kg air-flaps

AIRFLOW DIRECTION "OUT": INTAKE FILTER FPO 118

Art. No. Depth in enclosure Weight (approx.) Filter mat
11881.0-30 22 mm 0.2 kg ISO coarse 55 % acc. to ISO 16890 (G3), initial gravimetric arrestance 57 %

FILTER MAT FM 086

Filter class 118 x 118 mm Initial gravimetric arrestance 1 packing unit
ISO coarse 55 % acc. to ISO 16890 (G3) Art. No. 08634.0-00 57 % 5 pieces

TECHNICAL DRAWINGS

FPI 018/FPI 118
FPO 018/FPO 118

Stego Fiches techniques

Pays et langue Nom du fichier Lien de téléchargement
United States (English) stego-EN_54310.pdf Télécharger
Deutschland (Deutsch) stego-DE_71351.pdf Télécharger
Italy (Italiano) stego-IT_60429.pdf Télécharger

Demande de devis