Zander SR3D 472272 Safety Relay
Zander SR3D 472272 Safety Relay
Code: SR3D
Marke: Zander Aachen
| 
			 Feature  | 
			
			 Value  | 
		
| 
			 SR3D  | 
			|
| 
			 Safety function  | 
			
			 Emergency stop monitoring, safety guard monitoring,  | 
		
| 
			 Certified according to  | 
			
			 EN 60204-1; DIN EN ISO 13849-1; EN 62061; EN 50156-1;  | 
		
| 
			 Approvals  | 
			
			 CE, TUV, GL  | 
		
| 
			 Supply voltage  | 
			
			 AC/DC 24 V / AC 115 V / AC 230 V  | 
		
| 
			 Number of safe relay contacts  | 
			
			 3  | 
		
| 
			 Max. switching capability of safe relay contacts  | 
			
			 8 A / 250 VAC resistive load  | 
		
| 
			 Number of auxiliary relay contacts  | 
			
			 1  | 
		
| 
			 Number of non time-delayed contacts  | 
			
			 3  | 
		
| 
			 Number of time-delayed contacts  | 
			
			 -  | 
		
| 
			 Starting behavior  | 
			
			 Automatic start or manual, monitored start  | 
		
| 
			 PL; Cat.; SILCL (EN ISO 13849-1; EN 62061)  | 
			
			 PL e; Cat. 4; SILCL 3  | 
		
| 
			 Width  | 
			
			 22.5 mm  | 
		
| 
			 Order No. fixed screw terminals  | 
			
			 472272 (24 V) / 472271 (115 V) / 472270 (230 V)  | 
		
| 
			 Order No. plug-in screw terminals  | 
			
			 474272 (24 V) / 474271 (115 V) / 474270 (230 V)  | 
		
| 
			 Order No. push-in twin spring connector  | 
			
			 475272 (24 V) / 475271 (115 V) / 475270 (230 V)  | 
		
| 
			 Order No. EKLS4; set of plug-in screw terminals  | 
			
			 472592  | 
		
| 
			 Order No. EKLT4; set of push-in twin spring connectors  | 
			
			 472595  | 
		
| 
			 Order No. Spacer for a defined minimum distance between two safety relays (see derating)  | 
			
			 472596  | 
		
Zander Aachen Datenblätter
| Land Und Sprache | Dateinamen | Link Herunterladen | 
| Zander-Aachen-EN_42085.pdf | Downloaden | |
| sr3d-safety-emergency-stop-relay-50156-1_67358.pdf | Downloaden | 