Stego FPI/FPO 018 | UP TO 536 M³/H (223 X 223 MM) Filter Fan Plus

  • Stego FPI/FPO 018 | UP TO 536 M³/H (223 X 223 MM) Filter Fan Plus

Stego FPI/FPO 018 | UP TO 536 M³/H (223 X 223 MM) Filter Fan Plus

Code: FPI/FPO 018 | UP TO 536 M³/H (223 X 223 MM)
Marke: Stego

Axial fan, ball bearing

service life L10 at +40 °C (+104 °F): min. 56,000 h
rotor metal

Connection 3-pole clamp for 2.5 mm², clamping torque 0.8 Nm max.
Casing, hood, flaps plastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out 223 x 223+1 mm
Mounting frame 4 built-in ratchet braces for mounting
(6 notches for wall thickness 1-4 mm).
Additional use of screws possible if needed1.
Filter mat ISO coarse 55 % acc. to ISO 16890 (G3),
initial gravimetric arrestance 57 %
Filter material synthetic fibre with progressive construction,
temperature resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH, reusable
Operating temperature -25 to +65 °C (-13 to +149 °F)
Storage temperature -40 to +70 °C (-40 to +158 °F)
Operating/Storage humidity max. 75 % RH (non-condensing)
Protection type/Protection class IP54 / I (earthed)
Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
Approvals VDE, UL File No. E234324, EAC
Note other voltages on request

1 Drilling marks for screw mounting are indicated on mounting frame.

AIRFLOW DIRECTION "IN": FILTER FAN FPI 018

Art. No. Operating voltage Air volume,
free flow
Air volume
with exit filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01873.0-30 AC 230 V, 50/60 Hz 305 m³/h 271 m³/h 300/340 mA 64 W 64 dB (A) 147 mm 2.4 kg G3
01873.9-30 AC 115 V, 50/60 Hz 332 m³/h 293 m³/h 600/700 mA 81 W 67 dB (A) 147 mm 2.4 kg G3

AIRFLOW DIRECTION "IN": EXIT FILTER FPI 118

Art. No. Depth in enclosure Weight (approx.) Air outlet
11873.0-00 46 mm

0.6 kg

air-flap outlet technology

AIRFLOW DIRECTION "OUT": FILTER FAN FPO 018

Art. No. Operating
voltage
Air volume,
free flow
Air volume
with intake filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01883.0-00 AC 230 V, 50/60 Hz 536 m³/h 281 m³/h 300/340 mA 64 W 65 dB (A) 147 mm 2.4 kg air-flaps
01883.9-00 AC 115 V, 50/60 Hz 581 m³/h 310 m³/h 600/700 mA 81 W 68 dB (A) 147 mm 2.4 kg air-flaps

AIRFLOW DIRECTION "OUT": INTAKE FILTER FPO 118

Art. No. Depth in enclosure Weight (approx.) Filter mat
11883.0-30 25 mm 0.5 kg ISO coarse 55 % acc. to ISO 16890 (G3), initial gravimetric arrestance 57 %

FILTER MAT FM 086

Filter class 215 x 215 mm Initial gravimetric arrestance 1 packaging unit
ISO coarse 55 % acc. to ISO 16890 (G3) Art. No. 08636.0-00 57 % 5 pieces

TECHNICAL DRAWINGS

FPI 018/FPI 118
FPO 018/FPO 118

Stego Datenblätter

Land Und Sprache Dateinamen Link Herunterladen
United States (English) stego-EN_54310.pdf Downloaden
Deutschland (Deutsch) stego-DE_71351.pdf Downloaden
Italy (Italiano) stego-IT_60429.pdf Downloaden

Fordern Sie ein Angebot an